Ø If height of ladder is more than 2.1m then ladder should be provided with safety loop.
Ø Ladder step interval should not be more than 300mm.
Ø Provide at least main height clearance from over head beam.
Ø Stair way slope from horizontal should be in range 45 to 60 degree.
All manually operated valves shall be accessible from floor or from platform.
Ø Dead-end platforms greater than 6m long are prohibited because of confusion arises from an emergency or panic situation .An individual might select an escape path which would lead to such a dead end.
Ø Toe plate shall be provided on edge of all platform areas and around platform openings except platform entrance and exit location.
Ø Ladder should be generally arranged for side exit and ladder step should not exceed 300mm.